NOJA Power has released a guide that explores practical applications for less commonly deployed features in new and improved recloser protection systems.
NOJA Power said that protection features such as overcurrent and conventional earth fault are ubiquitous in network protection assets, but improvements in protection technologies are continuous and a vast new list of protection capabilities are now available.
NOJA Power explores some of the less commonly applied protection elements – such as voltage sag, broken conductor protection and harmonic protection – all of which are featured in the company’s OSM Recloser system, available to all users through current firmware or by means of a simple upgrade.
Voltage sag
Dubbed UV4 in NOJA Power’s OSM Recloser, Voltage Sag protection provides a technique for distinguishing between a conductor down scenario and a blown fuse or bridge.
Based on a Cigre paper presented at the 2015 SEAPAC event, the fundamental principle of operation is the difference in voltage signature between the two scenarios. UV4 evaluates voltage sags on individual phases of the protected line, categorising them as blown fuses or downed conductors.
As the detection is at a downstream unit, the information is fed back via SCADA allowing for operators to trip upstream breakers, isolating the fault. NOJA Power said that traditional overcurrent would not catch this fault, and earth fault may not be sufficiently sensitive to detect either of the scenarios.
ANSI 46 BC – broken conductor protection
Broken conductor protection is ratio analysis for power systems engineers. By dividing the negative sequence current by the positive sequence current, the magnitudes of either quantity is removed. NOJA Power said that in cases of broken conductors, the ratio tends to be above 20 per cent I2/I1.
Therefore, regardless of load current or network impedance, the ratio allows for detection of faults which conventional overcurrent and earth fault miss.
With an operating quantity estimate of 20 per cent, utilities can gain visibility of this class of faults.
Harmonic protection
As networks operate with increased penetration of inverter power electronics in other non-linear loads, harmonics are becoming a greater issue. NOJA Power said that harmonic issues often go undetected, until a costly failure of capital equipment such as a transformer due to excess heating from harmonics.
NOJA Power’s OSM Recloser provides harmonic protection, allowing utilities to alarm via SCADA or even trip the recloser based on harmonic levels present. Harmonic protection can be a simple method for mitigating the risk of costly equipment failure, while providing insights for problem connection sites.
NOJA Power Group Managing Director, Neil O’Sullivan, said, “As distribution networks become more complicated with more distributed generation connected every month, the protection schemes necessary to protect our distribution networks are also becoming more complicated and require these advanced elements to provide the required solution.”
These three protection elements are a few of the less commonly applied features in the NOJA Power OSM Recloser, but each provide significant value in their own niche.
To learn more, contact your local NOJA Power distributor or visit www.nojapower.com.au